The difference between of pressure sensor 5V Vs 10V analogue outputs?

Pressure sensors offer a variety of voltage output options — so what actually separates one analogue voltage output from another? Let’s take a look.


Каталог

As controllers that read sensor signals have evolved, designers now have far more flexibility. Many output options differ only slightly — some manufacturers keep an edge through custom designs, while others have specific benefits. The output types discussed here all need at least a 10 VDC supply (0–10 V and 1–10 V outputs typically require 12 VDC). The 0.5–4.5 V ratiometric output is traditionally powered from a 5 VDC regulated supply, although other arrangements do exist. Millivolt outputs have their own advantages too, but this piece focuses on amplified voltage outputs from pressure sensors.

Zero-referenced outputs

Traditional pressure sensor outputs include 0–5 V and 0–10 V. In Europe it’s common to use zero-referenced outputs that sit at 0 V when the pressure is zero. These sensors can be built as three-wire or four-wire units. The advantage of 0–10 V is obvious — it gives you twice the span of 0–5 V. The main drawback, though, is that at zero pressure there’s no signal, so you can’t tell whether there really is no pressure or if the sensor has failed (for instance a cut wire, a damaged sensing element or circuit over-voltage). Take water pressure monitoring — if the sensor reads 0 V, the system can’t distinguish between genuinely no pressure and a broken sensor. That ambiguity can lead to pump control failures and, in the worst case, flooding.

ВФ5837Ц сензор притиска
WF5837F Sensors

Outputs that still show a voltage at zero pressure

To get around that problem, there are sensors that still give a voltage at zero pressure — WF offers variants such as 1–5 V, 1–6 V, 0.25–5 V and 1–10 V. The 1–5 V type is the most common: it outputs 1 V at zero pressure and gives a 4 V span for measurement, so it provides a useful “alive” indication. The 1–6 V and 1–10 V options suit applications needing a wider span while still having a non-zero signal at zero pressure. A 0.5–2.5 V output is often used in remote sensing, particularly for battery- or solar-powered devices — the lower voltages and currents help stretch operating life. A 0.5 V zero reading clearly shows the sensor is working; the 2.5 V span still gives you adequate resolution for pressure or level measurement.

Intelligent fault signalling

Industrial pressure sensors are getting smarter. With modern electronics and microcontrollers, sensors can be programmed to signal a “fault” condition. You can set the output to go outside the normal range (for example roughly 10% below the minimum or above the maximum) to flag an issue. So if an overpressure event ruptures the isolation diaphragm, a 1–5 V sensor can be configured to output less than 1 V or more than 5 V to alert the controller. In pump control systems this kind of feature helps avoid flooding, dry running or excessive wear.

WF pressure sensors cover a very wide measurement range — from under 1 PSI up to 100,000 Пси.

Закључак

Pick the output that balances span/resolution, fault detectability, and power/compatibility — 1–5 V is a safe, all-round choice; 0–10 V when you want more span; low-voltage outputs for power-limited remote systems.

Горњи увод огреботине само површину апликација технологије сензора притиска. И даље ћемо истражити различите врсте сензорских елемената који се користе у различитим производима, Како раде, и њихове предности и недостатке. Ако желите више детаља о томе о чему се овде расправља, Касније можете да проверите повезани садржај у овом водичу. Ако сте притиснути време, Овде можете да кликнете и да преузмете детаље ових водича Подаци о сензору притиска ваздуха ПДФ.